MAX 100-150KTL3-X LV
On-grid PV InverterCommercial & Industrial PV Inverter

Growatt commercial PV string-inverter review

Growatt MAX 100-150KTL3-X LV Commercial Inverter Family

MAX 100/110/120/125KTL3-X LV plus the separate MAX 150KTL3-X LV The verified source tables show 1100 V maximum and ten MPPTs; 100-125 kW lists two strings and 32 A per tracker, while 150 kW lists 45 A per tracker with a mixed two/three-string allocation On the AC side, three-phase 220/380 or 230/400 V, covering 100-150 kW and 110-165 kVA maximum apparent power 98.8% maximum Select one complete model, voltage route and destination document set before quotation; family maxima, optional protection and certificate lists do not apply automatically to every member.

Released members: MAX 100/110/120/125KTL3-X LV plus the separate MAX 150KTL3-X LVPV route: 1100 V maximum and ten MPPTs; 100-125 kW lists two strings and 32 A per tracker, while 150 kW lists 45 A per tracker with a mixed two/three-string allocationAC route: three-phase 220/380 or 230/400 V, covering 100-150 kW and 110-165 kVA maximum apparent powerEnclosure and efficiency: IP66; 84 kg for 100-125 kW and 93 kg for 150 kW; 98.8% maximum
Build Your RFQ

Current source identity: official Growatt May 2026 MAX 100-125KTL3-X LV and MAX 150KTL3-X LV datasheet set. The 150 kW member has a separate table with higher tracker current, different string allocation, dimensions, mass and optional AFCI/anti-PID rows; it is not another column of the 100-125 kW table.

Current document status

Before quotation, obtain the exact full model and suffix, current datasheet and manual, destination certificate/model schedule, approved grid profile, PV string schedule, AC collection and protection design, AFCI/PID/SPD option status, connector and monitoring hardware, firmware, warranty, packing and written substitution rules.

Current family evidence

Preserve the member, DC-input and AC-voltage boundaries

The official tables define a family, not one interchangeable column.

Released model columns

MAX 100/110/120/125KTL3-X LV plus the separate MAX 150KTL3-X LV

PV and MPPT architecture

1100 V maximum and ten MPPTs; 100-125 kW lists two strings and 32 A per tracker, while 150 kW lists 45 A per tracker with a mixed two/three-string allocation

AC interconnection route

three-phase 220/380 or 230/400 V, covering 100-150 kW and 110-165 kVA maximum apparent power

Protection and physical record

Type II DC/AC surge and string detection are listed; AFCI/anti-PID status differs between the 100-125 kW and 150 kW files. IP66; 84 kg for 100-125 kW and 93 kg for 150 kW

commercial PV inverter RFQ inputs

Six checks before fixing the inverter member and BOM

Array, AC collection, options and destination evidence must map to the same released model.

Full model and destination

State the complete model/suffix, quantity, country, utility, service voltage/frequency, export or PPC rule and required grid-code, safety and EMC evidence.

PV string and MPPT schedule

Provide module Voc/Vmp/Isc/Imp, temperature coefficients, strings per tracker and orientation; verify cold Voc, operating voltage, tracker current, short-circuit allowance and connector/cable ratings.

AC collection and grid

Define inverter AC voltage, conductor/busbar, breaker or switchgear, transformer where applicable, grounding, fault level, voltage drop, reactive-power duty and point-of-connection limit.

Protection and ordering options

Freeze DC switch, SPD, AFCI, anti-PID, night SVG or other options by exact ordering code. A source row marked optional or variant-specific is not standard equipment for every member.

Monitoring and plant control

Confirm RS485/USB, Wi-Fi/LAN/4G/RF/PLC hardware, logger or ShineMaster/SEM route, meter/PPC/export control, communications-loss behavior, firmware and account ownership.

Documents and commercial control

Request current datasheet/manual, certificate model list, SLD and settings, warranty, packing, serial traceability, accessories, lead time and written approval for any substitution.

Family, option and performance boundaries

Do not move family maxima or certificate coverage between columns

The exact member, voltage route, firmware, array and destination documents remain controlling.

Variant tables remain separate

The 150 kW member has a separate table with higher tracker current, different string allocation, dimensions, mass and optional AFCI/anti-PID rows; it is not another column of the 100-125 kW table.

Maximum efficiency is not yield

98.8% maximum This is a datasheet maximum, not an annual-energy or every-operating-point guarantee; model, loading, temperature, clipping, wiring and availability affect yield.

Optional protection needs an order code

Type II DC/AC surge and string detection are listed; AFCI/anti-PID status differs between the 100-125 kW and 150 kW files. Confirm factory option, external devices, settings, applicable manual and destination design instead of relying on a family headline.

Certificates do not transfer automatically

A downloads list may span members, suffixes and countries. Require the ordered full model on the current certificate schedule and use the destination grid settings and commissioning record.

Continue the commercial PV review

Connect the exact inverter to the project design and controlled BOM

Use the solution and BOM guides to coordinate electrical interfaces, documents and responsibility boundaries.

Growatt MAX 100-150KTL3-X LV Commercial Inverter Family FAQ

Questions to close before releasing the inverter order

One exact member and one matching evidence set should support the quotation.

Which model columns are covered by the verified source?

MAX 100/110/120/125KTL3-X LV plus the separate MAX 150KTL3-X LV

Can one PV string design be used across the whole family?

No. 1100 V maximum and ten MPPTs; 100-125 kW lists two strings and 32 A per tracker, while 150 kW lists 45 A per tracker with a mixed two/three-string allocation Check the exact member's tracker/string allocation, voltage and current against the selected module and site temperature.

Are AFCI, PID and other protection functions standard on every member?

Do not assume that. Type II DC/AC surge and string detection are listed; AFCI/anti-PID status differs between the 100-125 kW and 150 kW files. Confirm the complete ordering code, external protection design, manual and destination requirements.

What should the RFQ freeze?

Freeze full model/suffix, PV strings, AC voltage and collection, transformer/grid interface, protection/options, monitoring/PPC, certificate set, firmware, warranty, accessories and quantity.

Prepare an exact Growatt MAX 100-150KTL3-X LV Commercial Inverter Family RFQ

Send the full member and suffix, module/string schedule, AC and grid design, protection/options, monitoring/control, destination documents, accessories and quantity.

Start with the product, application or project information you have. We can help identify the remaining configuration, document or delivery questions before a final quotation.

Verify the Inverter Configuration
Chat with Us